Fire resistance of steel framed buildings - Fire damage assessment of hot rolled structural steel

Topics Covered

Reasons for fire damage
Behaviour of BS EN 10025 grade S275 steel (formerly grade 43)
Behaviour of BS EN 10025 grade S355 steel (formerly grade 50)
Re-use of fire-damaged steel
Connections and foundations

The assessment of fire damaged hot rolled structural steel is an area in which most engineers and architects have little practical experience. On many occasions fire affected steelwork shows little or no distortion resulting in considerable uncertainty regarding its re-usability. This is particularly true in situations whose fire has resulted in some parts of the structure exhibiting little or no damage alongside areas where considerable damage and distortion are clearly visible.

The principal source of information on this subject in the Corus Publication ‘The Reinstatement of Fire Damaged Steel and Iron Framed Structures. Its main conclusions are summarised here.

Reasons for fire damage

All materials weaken with increasing temperature and steel is no exception. Strength loss for steel is generally accepted to begin at about 300ºC and increases rapidly after 400ºC, by 550ºC steel retains about 60% of its room temperature yield strength. This is usually considered to be the failure temperature for structural steel. However, in practice this is a very conservative assumption; low loads, the insulating effects of concrete slabs, the restraining effects of connections etc. mean that real failure temperatures can be as high as 750ºC or even higher for partially exposed members.

Behaviour of BS EN 10025 grade S275 steel (formerly grade 43)

A modern grade S275 hot rolled structural steel section, subjected to fire conditions which raises its temperature above 600ºC, may suffer some deterioration in residual properties on cooling. In no situation however, whatever the fire temperature, will the room temperature yield stress or the tensile strength fall further than 10% below their original values. Thus, where it can be safely concluded that the steel members will be utilised to less than 90% of their maximum load bearing capacity or that any loss in strength will not bring the properties below the guaranteed minimum, replacement should not be considered necessary providing the member satisfies all other engineering requirements (e.g. straightness).

Behaviour of BS EN 10025 grade S355 steel (formerly grade 50)

Grade S355 hot rolled structural steel also suffers losses in residual yield and tensile strength when subjected to temperature over 600ºC in fire. High strength steels, of which grade S355 is typical, obtain their characteristics as the result of the addition of strengthening elements, typically vanadium and niobium. At high temperatures these elements tend to precipitate out of the matrix creating a coarse distribution. As a result the reduction in yield strength at room temperature after the steel has been heated to temperatures above 600ºC, may be proportionately greater than for unalloyed mild steels.

Re-use of fire damaged steel

An often quoted general rule for fire affected hot rolled structural steels is that if the steel is straight and there are no obvious distortions then the steel is steel fit for use. At 600ºC the yield strength of steel is equal to about 40% of its room temperature value; it follows therefore that any steel still remaining straight after the fire and which had been carrying an appreciable load was probably not heated beyond 600ºC, would not have undergone any metallurgical changes and will probably be fit for re-use.

 However, where the load in the fire was less than the full design load, and also with high strength steels, this cannot always be held to be true. In such cases it is recommended that hardness tests are carried out on the affected steel. In practice it is recommended that, in all instance, some hardness tests should be carried out. For grade S275 steel, if the ultimate tensile strength resulting from the tests are within the range specified in Table 2 then the steel is reusable.

For grade S355 steel additional tensile test coupons should be taken from fire affected high strength steel members when hardness tests show that :

1- There is more than 10% difference in hardness compared to non-fire affected steelwork. Or

2- Hardness test results indicate that the strength is within 10% of the specified minimum.

Where deflections are visible, general guidelines on the maximum permissible levels of deflection to ensure satisfactory performance are difficult to specify. The amount of deflection or distortion must be checked so that its effect under load can be calculated to ensure that permissible stresses are not exceeded and the functioning of the building is not impaired. Therefore every building should be considered as a separate case and the structural engineer involved in the reinstatement exercise must decide what level is acceptable to satisfy the relevant Codes.

Connections and foundations

The tensile strength reduction for grade 4.6 bolts is similar to that for S275 steel. For grade 8.8 bolts, which are heat treated in manufacture, the residual strength reduction is more marked if the material temperature has exceeded 450ºC. The residual strength of these bolts falls to 80% and 60% after reaching temperatures of 600ºC and 800ºC respectively.

To err on the side of caution it is recommended that bolts should be replaced if they show any sign of having been heated e.g. blistered paint, smooth grey scaled surface.

Contraction of heated members after the fire can cause distortion of connections. When carrying out an inspection of a fire damaged building it is recommended that special care is taken in inspecting the connections for cracking of welds, end plate damage, bolt failure etc. A number of bolts should be removed to inspect for distortion. Similar care should be taken when inspecting foundations for bolt failure, concrete cracking etc.

Source: Corus