Air conditioning condenser cooling systems. Cost considerations

Summary

Presents an updated version of a study carried out by BSRIA in 1987 of the relative costs of alternative wet  and dry condenser cooling systems serving the chillers of an air conditioned office building. Since then,  more specific water treatment and maintenance requirements for cooling towers have been published to  minimise the risk of an outbreak of Legionnaires' disease, and this has modified the cost assessment. Revises  the original case study capital and running costs to late 1989 prices and assesses the current water treatment  and maintenance costs. States that the revised assessment of overall costs shows that up to a cooling load  capacity of 1200kW the packaged air cooled chiller option is cheaper than a cooling tower or dry cooler  system with separate chillers. The cooling tower system however requires the least roof space.

Primary Author(s): Smith:M:H., Stewart:L:J.

Source: BSRIA 1990, Technical Memorandum TM 1/90, 20pp, 10 figs, 5 tabs, 5 refs

             BSRIA Abstract No. 9001397